Listec® SEC15 d-LIST Sensor Cable

 

SEC15 CableThe hermetically sealed sensor cable contains temperature sensors, which, depending on the specification, are placed at selectable intervals. The sensors are electronically connected by a flat flexible cable.

The flat flexible cable and the temperature sensors are surrounded by a filling material, which in turn is covered by an aluminium shield that protects against electro-magnetic interference. A flame retarding, halogen free cable sheath completes the sealed structure of the sensor cable.

The cable can measure temperatures from -40°C to +85°C (for short periods +120°C) with a resolution of 0.1°C.

On account of its maintenance and adjustment free operation, the sensor cable can be used in areas which are not or are only partly accessible during normal operation.

Due to the constant interrogation of the temperature sensors by the control unit SCU 800, a functional check of all temperature sensors is always given.

Specifications:

Cable Construction

Sensor Spacing

  • Temperature sensors mounted on a 2 core flat flexible cable.
  • Filling material with strain relief.
  • Aluminium shield.
  • Cable sheath.
Freely selectable, minimum distance of 0.5m. Standard spacing: 1,2,3,4 & 5m.

Sensor Marking

Cable Specifications

A 3-digit consecutive number on the cable sheath marks the position of each sensor in the cable.
Diameter:
approx. 15mm
Min. bending radius:
0.25m
Max. continuous length:
2000m
Cable sheath:
halogen free,
flame retarding,
acc. to DIN VDE 0207, part 24
Sheath colour:
grey
Operating temp. range:
-40°C ... +85°C
short period +120°C
Mounting temperature:
+10°C

Measuring Point Specifications

 
Measuring range:
-40°C ... +100°C
 
Resolution:
0.1°C

SEC15 Cable Cross Section
SEC15 Cross Section